Can the ground attached to neutral fool a receptacle tester?Can I ground my workbench using an unused...

Is Texas Instrument wrong with their pin number on TO-92 package?

Multirow in tabularx?

Identification of vintage sloping window

Email address etiquette - Which address should I use to contact professors?

What is my malfunctioning AI harvesting from humans?

What is the length of pair of wires after twisting them around each other?

Why does Intel's Haswell chip allow FP multiplication to be twice as fast as addition?

Ex-contractor published company source code and secrets online

How are you supposed to know the strumming pattern for a song from the "chord sheet music"?

How can I solve for the intersection points of two ellipses?

Continuous vertical line using booktabs in tabularx table?

Tikzpicture - finish drawing a curved line for a cake slice

elisp regular expression build problem

On the Rømer experiments and the speed if light

ICO or PNG Format?

Not going forward with internship interview process

Does a code snippet compile? Or does it get compiled?

constant evaluation when using differential equations.

How should an administrative assistant reply to student addressing them as "Professor" or "Doctor"?

Generate Brainfuck for the numbers 1–255

Te-form and かつ and も?

Wherein the Shatapatha Brahmana it was mentioned about 8.64 lakh alphabets in Vedas?

How is this kind of structure made?

Plausibility of Ice Eaters in the Arctic



Can the ground attached to neutral fool a receptacle tester?


Can I ground my workbench using an unused outlet's neutral?Does a neutral-to-ground voltage of 0.0 indicate a bootleg ground?Outlet with ground wire attached to socket ground and neutralOdd Problem Testing Series OutletsGFCI Outlet Trips with Receptacle TEST Button, but not with GFCI Outlet Tester ToolGFCI tester doesn't trip GFCI. Bootleg ground?Grounding issues and ground testerWhy is neutral wired to ground at this switch?Trying to add an outlet on other side of wall, 3 pairs of white/black wires and groundIf a receptacle is added from a switch box, will the receptacle only work when the switch is off?






.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty,.everyoneloves__bot-mid-leaderboard:empty{ margin-bottom:0;
}







2















I'm using a basic outlet tester like the one from picture below. Let's say someone wired the ground to the neutral in some outlet, to provide a fake ground. What would the tester report? Would it be "CORRECT" or would it be something else?



In case it reports "CORRECT" (wrongly, of course), is there some easy way to test that the ground is fake? By easy I mean not having to open the outlet...



enter image description here










share|improve this question




















  • 1





    put a heavy load on the power outlet ... measure the voltage between neutral and ground ... zero voltage indicates that the two are shorted at the plug

    – jsotola
    5 hours ago




















2















I'm using a basic outlet tester like the one from picture below. Let's say someone wired the ground to the neutral in some outlet, to provide a fake ground. What would the tester report? Would it be "CORRECT" or would it be something else?



In case it reports "CORRECT" (wrongly, of course), is there some easy way to test that the ground is fake? By easy I mean not having to open the outlet...



enter image description here










share|improve this question




















  • 1





    put a heavy load on the power outlet ... measure the voltage between neutral and ground ... zero voltage indicates that the two are shorted at the plug

    – jsotola
    5 hours ago
















2












2








2








I'm using a basic outlet tester like the one from picture below. Let's say someone wired the ground to the neutral in some outlet, to provide a fake ground. What would the tester report? Would it be "CORRECT" or would it be something else?



In case it reports "CORRECT" (wrongly, of course), is there some easy way to test that the ground is fake? By easy I mean not having to open the outlet...



enter image description here










share|improve this question














I'm using a basic outlet tester like the one from picture below. Let's say someone wired the ground to the neutral in some outlet, to provide a fake ground. What would the tester report? Would it be "CORRECT" or would it be something else?



In case it reports "CORRECT" (wrongly, of course), is there some easy way to test that the ground is fake? By easy I mean not having to open the outlet...



enter image description here







electrical receptacle grounding neutral grounding-and-bonding






share|improve this question













share|improve this question











share|improve this question




share|improve this question










asked 10 hours ago









fernacolofernacolo

1591 silver badge5 bronze badges




1591 silver badge5 bronze badges











  • 1





    put a heavy load on the power outlet ... measure the voltage between neutral and ground ... zero voltage indicates that the two are shorted at the plug

    – jsotola
    5 hours ago
















  • 1





    put a heavy load on the power outlet ... measure the voltage between neutral and ground ... zero voltage indicates that the two are shorted at the plug

    – jsotola
    5 hours ago










1




1





put a heavy load on the power outlet ... measure the voltage between neutral and ground ... zero voltage indicates that the two are shorted at the plug

– jsotola
5 hours ago







put a heavy load on the power outlet ... measure the voltage between neutral and ground ... zero voltage indicates that the two are shorted at the plug

– jsotola
5 hours ago












3 Answers
3






active

oldest

votes


















4














The tester will show "correct". Opening the outlet is the only way to check it that I know of.






share|improve this answer

































    4














    The tester can't tell the difference. One way to look at is that electrically, since neutral and ground are already bonded at one location (normally the main panel), the electrons don't know the difference. But the other way to think about it is to look at what the tester is actually doing.



    What do the Lights Indicate?



    These testers are actually 3 simple lights connected as follows (left to right on your particular tester, others may vary):




    • Hot to Ground


    This will light up provided that Hot is indeed Hot (and not Neutral) and Ground is functional.



    Note that Ground being functional in this context does not mean "connected to a water pipe or rebar or a ground rod", though that alone might be enough. It means "ground connected to neutral in the main panel".



    That also means that if Ground is connected directly to neutral in this receptacle box, the tester does not see that as a problem.




    • Hot to Neutral


    This will light up provided that Hot is indeed Hot (and not Neutral) and Neutral is functional.




    • Neutral to Ground


    Since Neutral and Ground are bonded in the main panel, this light is normally off. Connecting them inside the receptacle box won't make any difference. Where this does light up is if something else is really messed up so that current flows between neutral and ground. The most likely scenarios are Hot swapped with either Neutral or Ground, so the tester "identifies" those conditions but those are really not guarantees as there are other possible situations.



    What do the Light Combinations Mean?



    There are 8 possible combinations. But "all on" would be really strange (but possible if someone wires a 120V receptacle to a 240V breaker) so that is not included. The other combination not included is Off, Off, On. That would mean current flowing only between Ground and Neutral (the exact opposite of this question), and no current flowing between Hot & Neutral or between Hot & Ground, which would be pretty hard to do (Open Hot + Hot/Neutral swapped?)



    Just remember, the titles assigned are based on the most common scenarios but are not the only possible problems.




    • Off, On, Off = Open Ground - Hot to Neutral but no Hot to Ground


    • On, Off, Off = Open Neutral - Hot to Ground but no Hot to Neutral


    • Off, Off, Off = Open Hot - But really means "nothing at all" - e.g., could be "Open Ground + Open Neutral but Hot OK" - so don't assume this means there is no hot wire present - that could be a deadly mistake!


    • On, Off, On = Hot/Ground Reverse - Hot to Ground OK, but not Hot to Neutral, so the likely situation is that the Hot & Ground wires are reversed but it could be something else.


    • Off, On, On = Hot/Neutral Reverse - Hot to Neutral OK, but not Hot to Ground, so the likely situation is that the Hot & Neutral wires are reversed but it could be something else.


    • On, On, Off = Correct - Except, it really only tells you that Hot is in the right place and that all Ground & Neutral are, collectively, correct. It does not tell you, for example, if Ground & Neutral are reversed or, as originally asked, if Ground & Neutral are combined.







    share|improve this answer



































      1














      Yes, it will misread. Because magic-8-ball testers are built for one thing: a quick pass/fail test for brand new wiring you just installed.



      Obviously, in new wiring, you don't have a bunch of the kinds of problems you have in old wiring, like people bootlegging ground off neutral. The device is simply not made to solve those problems.



      So if you misuse the tool to test old wiring, the reports (what it says on the label) will often be misleading, and will send you on wild goose chases. That's why I call it a magic 8-ball tester! An actual magic-8-ball would be about as reliable. It is useful in two ways:




      • The lights themselves can give you hints (provided you know how they are connected, see manassehkatz's discussion)

      • The "GFCI test" button can be helpful when testing downline receptacles fed off a GFCI elsewhere.


      With old wiring there's no substitute for opening it up and having a look.






      share|improve this answer






























        Your Answer








        StackExchange.ready(function() {
        var channelOptions = {
        tags: "".split(" "),
        id: "73"
        };
        initTagRenderer("".split(" "), "".split(" "), channelOptions);

        StackExchange.using("externalEditor", function() {
        // Have to fire editor after snippets, if snippets enabled
        if (StackExchange.settings.snippets.snippetsEnabled) {
        StackExchange.using("snippets", function() {
        createEditor();
        });
        }
        else {
        createEditor();
        }
        });

        function createEditor() {
        StackExchange.prepareEditor({
        heartbeatType: 'answer',
        autoActivateHeartbeat: false,
        convertImagesToLinks: false,
        noModals: true,
        showLowRepImageUploadWarning: true,
        reputationToPostImages: null,
        bindNavPrevention: true,
        postfix: "",
        imageUploader: {
        brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
        contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
        allowUrls: true
        },
        noCode: true, onDemand: true,
        discardSelector: ".discard-answer"
        ,immediatelyShowMarkdownHelp:true
        });


        }
        });














        draft saved

        draft discarded


















        StackExchange.ready(
        function () {
        StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f171022%2fcan-the-ground-attached-to-neutral-fool-a-receptacle-tester%23new-answer', 'question_page');
        }
        );

        Post as a guest















        Required, but never shown

























        3 Answers
        3






        active

        oldest

        votes








        3 Answers
        3






        active

        oldest

        votes









        active

        oldest

        votes






        active

        oldest

        votes









        4














        The tester will show "correct". Opening the outlet is the only way to check it that I know of.






        share|improve this answer






























          4














          The tester will show "correct". Opening the outlet is the only way to check it that I know of.






          share|improve this answer




























            4












            4








            4







            The tester will show "correct". Opening the outlet is the only way to check it that I know of.






            share|improve this answer













            The tester will show "correct". Opening the outlet is the only way to check it that I know of.







            share|improve this answer












            share|improve this answer



            share|improve this answer










            answered 9 hours ago









            JACKJACK

            1,44110 bronze badges




            1,44110 bronze badges




























                4














                The tester can't tell the difference. One way to look at is that electrically, since neutral and ground are already bonded at one location (normally the main panel), the electrons don't know the difference. But the other way to think about it is to look at what the tester is actually doing.



                What do the Lights Indicate?



                These testers are actually 3 simple lights connected as follows (left to right on your particular tester, others may vary):




                • Hot to Ground


                This will light up provided that Hot is indeed Hot (and not Neutral) and Ground is functional.



                Note that Ground being functional in this context does not mean "connected to a water pipe or rebar or a ground rod", though that alone might be enough. It means "ground connected to neutral in the main panel".



                That also means that if Ground is connected directly to neutral in this receptacle box, the tester does not see that as a problem.




                • Hot to Neutral


                This will light up provided that Hot is indeed Hot (and not Neutral) and Neutral is functional.




                • Neutral to Ground


                Since Neutral and Ground are bonded in the main panel, this light is normally off. Connecting them inside the receptacle box won't make any difference. Where this does light up is if something else is really messed up so that current flows between neutral and ground. The most likely scenarios are Hot swapped with either Neutral or Ground, so the tester "identifies" those conditions but those are really not guarantees as there are other possible situations.



                What do the Light Combinations Mean?



                There are 8 possible combinations. But "all on" would be really strange (but possible if someone wires a 120V receptacle to a 240V breaker) so that is not included. The other combination not included is Off, Off, On. That would mean current flowing only between Ground and Neutral (the exact opposite of this question), and no current flowing between Hot & Neutral or between Hot & Ground, which would be pretty hard to do (Open Hot + Hot/Neutral swapped?)



                Just remember, the titles assigned are based on the most common scenarios but are not the only possible problems.




                • Off, On, Off = Open Ground - Hot to Neutral but no Hot to Ground


                • On, Off, Off = Open Neutral - Hot to Ground but no Hot to Neutral


                • Off, Off, Off = Open Hot - But really means "nothing at all" - e.g., could be "Open Ground + Open Neutral but Hot OK" - so don't assume this means there is no hot wire present - that could be a deadly mistake!


                • On, Off, On = Hot/Ground Reverse - Hot to Ground OK, but not Hot to Neutral, so the likely situation is that the Hot & Ground wires are reversed but it could be something else.


                • Off, On, On = Hot/Neutral Reverse - Hot to Neutral OK, but not Hot to Ground, so the likely situation is that the Hot & Neutral wires are reversed but it could be something else.


                • On, On, Off = Correct - Except, it really only tells you that Hot is in the right place and that all Ground & Neutral are, collectively, correct. It does not tell you, for example, if Ground & Neutral are reversed or, as originally asked, if Ground & Neutral are combined.







                share|improve this answer
































                  4














                  The tester can't tell the difference. One way to look at is that electrically, since neutral and ground are already bonded at one location (normally the main panel), the electrons don't know the difference. But the other way to think about it is to look at what the tester is actually doing.



                  What do the Lights Indicate?



                  These testers are actually 3 simple lights connected as follows (left to right on your particular tester, others may vary):




                  • Hot to Ground


                  This will light up provided that Hot is indeed Hot (and not Neutral) and Ground is functional.



                  Note that Ground being functional in this context does not mean "connected to a water pipe or rebar or a ground rod", though that alone might be enough. It means "ground connected to neutral in the main panel".



                  That also means that if Ground is connected directly to neutral in this receptacle box, the tester does not see that as a problem.




                  • Hot to Neutral


                  This will light up provided that Hot is indeed Hot (and not Neutral) and Neutral is functional.




                  • Neutral to Ground


                  Since Neutral and Ground are bonded in the main panel, this light is normally off. Connecting them inside the receptacle box won't make any difference. Where this does light up is if something else is really messed up so that current flows between neutral and ground. The most likely scenarios are Hot swapped with either Neutral or Ground, so the tester "identifies" those conditions but those are really not guarantees as there are other possible situations.



                  What do the Light Combinations Mean?



                  There are 8 possible combinations. But "all on" would be really strange (but possible if someone wires a 120V receptacle to a 240V breaker) so that is not included. The other combination not included is Off, Off, On. That would mean current flowing only between Ground and Neutral (the exact opposite of this question), and no current flowing between Hot & Neutral or between Hot & Ground, which would be pretty hard to do (Open Hot + Hot/Neutral swapped?)



                  Just remember, the titles assigned are based on the most common scenarios but are not the only possible problems.




                  • Off, On, Off = Open Ground - Hot to Neutral but no Hot to Ground


                  • On, Off, Off = Open Neutral - Hot to Ground but no Hot to Neutral


                  • Off, Off, Off = Open Hot - But really means "nothing at all" - e.g., could be "Open Ground + Open Neutral but Hot OK" - so don't assume this means there is no hot wire present - that could be a deadly mistake!


                  • On, Off, On = Hot/Ground Reverse - Hot to Ground OK, but not Hot to Neutral, so the likely situation is that the Hot & Ground wires are reversed but it could be something else.


                  • Off, On, On = Hot/Neutral Reverse - Hot to Neutral OK, but not Hot to Ground, so the likely situation is that the Hot & Neutral wires are reversed but it could be something else.


                  • On, On, Off = Correct - Except, it really only tells you that Hot is in the right place and that all Ground & Neutral are, collectively, correct. It does not tell you, for example, if Ground & Neutral are reversed or, as originally asked, if Ground & Neutral are combined.







                  share|improve this answer






























                    4












                    4








                    4







                    The tester can't tell the difference. One way to look at is that electrically, since neutral and ground are already bonded at one location (normally the main panel), the electrons don't know the difference. But the other way to think about it is to look at what the tester is actually doing.



                    What do the Lights Indicate?



                    These testers are actually 3 simple lights connected as follows (left to right on your particular tester, others may vary):




                    • Hot to Ground


                    This will light up provided that Hot is indeed Hot (and not Neutral) and Ground is functional.



                    Note that Ground being functional in this context does not mean "connected to a water pipe or rebar or a ground rod", though that alone might be enough. It means "ground connected to neutral in the main panel".



                    That also means that if Ground is connected directly to neutral in this receptacle box, the tester does not see that as a problem.




                    • Hot to Neutral


                    This will light up provided that Hot is indeed Hot (and not Neutral) and Neutral is functional.




                    • Neutral to Ground


                    Since Neutral and Ground are bonded in the main panel, this light is normally off. Connecting them inside the receptacle box won't make any difference. Where this does light up is if something else is really messed up so that current flows between neutral and ground. The most likely scenarios are Hot swapped with either Neutral or Ground, so the tester "identifies" those conditions but those are really not guarantees as there are other possible situations.



                    What do the Light Combinations Mean?



                    There are 8 possible combinations. But "all on" would be really strange (but possible if someone wires a 120V receptacle to a 240V breaker) so that is not included. The other combination not included is Off, Off, On. That would mean current flowing only between Ground and Neutral (the exact opposite of this question), and no current flowing between Hot & Neutral or between Hot & Ground, which would be pretty hard to do (Open Hot + Hot/Neutral swapped?)



                    Just remember, the titles assigned are based on the most common scenarios but are not the only possible problems.




                    • Off, On, Off = Open Ground - Hot to Neutral but no Hot to Ground


                    • On, Off, Off = Open Neutral - Hot to Ground but no Hot to Neutral


                    • Off, Off, Off = Open Hot - But really means "nothing at all" - e.g., could be "Open Ground + Open Neutral but Hot OK" - so don't assume this means there is no hot wire present - that could be a deadly mistake!


                    • On, Off, On = Hot/Ground Reverse - Hot to Ground OK, but not Hot to Neutral, so the likely situation is that the Hot & Ground wires are reversed but it could be something else.


                    • Off, On, On = Hot/Neutral Reverse - Hot to Neutral OK, but not Hot to Ground, so the likely situation is that the Hot & Neutral wires are reversed but it could be something else.


                    • On, On, Off = Correct - Except, it really only tells you that Hot is in the right place and that all Ground & Neutral are, collectively, correct. It does not tell you, for example, if Ground & Neutral are reversed or, as originally asked, if Ground & Neutral are combined.







                    share|improve this answer















                    The tester can't tell the difference. One way to look at is that electrically, since neutral and ground are already bonded at one location (normally the main panel), the electrons don't know the difference. But the other way to think about it is to look at what the tester is actually doing.



                    What do the Lights Indicate?



                    These testers are actually 3 simple lights connected as follows (left to right on your particular tester, others may vary):




                    • Hot to Ground


                    This will light up provided that Hot is indeed Hot (and not Neutral) and Ground is functional.



                    Note that Ground being functional in this context does not mean "connected to a water pipe or rebar or a ground rod", though that alone might be enough. It means "ground connected to neutral in the main panel".



                    That also means that if Ground is connected directly to neutral in this receptacle box, the tester does not see that as a problem.




                    • Hot to Neutral


                    This will light up provided that Hot is indeed Hot (and not Neutral) and Neutral is functional.




                    • Neutral to Ground


                    Since Neutral and Ground are bonded in the main panel, this light is normally off. Connecting them inside the receptacle box won't make any difference. Where this does light up is if something else is really messed up so that current flows between neutral and ground. The most likely scenarios are Hot swapped with either Neutral or Ground, so the tester "identifies" those conditions but those are really not guarantees as there are other possible situations.



                    What do the Light Combinations Mean?



                    There are 8 possible combinations. But "all on" would be really strange (but possible if someone wires a 120V receptacle to a 240V breaker) so that is not included. The other combination not included is Off, Off, On. That would mean current flowing only between Ground and Neutral (the exact opposite of this question), and no current flowing between Hot & Neutral or between Hot & Ground, which would be pretty hard to do (Open Hot + Hot/Neutral swapped?)



                    Just remember, the titles assigned are based on the most common scenarios but are not the only possible problems.




                    • Off, On, Off = Open Ground - Hot to Neutral but no Hot to Ground


                    • On, Off, Off = Open Neutral - Hot to Ground but no Hot to Neutral


                    • Off, Off, Off = Open Hot - But really means "nothing at all" - e.g., could be "Open Ground + Open Neutral but Hot OK" - so don't assume this means there is no hot wire present - that could be a deadly mistake!


                    • On, Off, On = Hot/Ground Reverse - Hot to Ground OK, but not Hot to Neutral, so the likely situation is that the Hot & Ground wires are reversed but it could be something else.


                    • Off, On, On = Hot/Neutral Reverse - Hot to Neutral OK, but not Hot to Ground, so the likely situation is that the Hot & Neutral wires are reversed but it could be something else.


                    • On, On, Off = Correct - Except, it really only tells you that Hot is in the right place and that all Ground & Neutral are, collectively, correct. It does not tell you, for example, if Ground & Neutral are reversed or, as originally asked, if Ground & Neutral are combined.








                    share|improve this answer














                    share|improve this answer



                    share|improve this answer








                    edited 4 hours ago

























                    answered 7 hours ago









                    manassehkatzmanassehkatz

                    16.1k1 gold badge23 silver badges50 bronze badges




                    16.1k1 gold badge23 silver badges50 bronze badges


























                        1














                        Yes, it will misread. Because magic-8-ball testers are built for one thing: a quick pass/fail test for brand new wiring you just installed.



                        Obviously, in new wiring, you don't have a bunch of the kinds of problems you have in old wiring, like people bootlegging ground off neutral. The device is simply not made to solve those problems.



                        So if you misuse the tool to test old wiring, the reports (what it says on the label) will often be misleading, and will send you on wild goose chases. That's why I call it a magic 8-ball tester! An actual magic-8-ball would be about as reliable. It is useful in two ways:




                        • The lights themselves can give you hints (provided you know how they are connected, see manassehkatz's discussion)

                        • The "GFCI test" button can be helpful when testing downline receptacles fed off a GFCI elsewhere.


                        With old wiring there's no substitute for opening it up and having a look.






                        share|improve this answer
































                          1














                          Yes, it will misread. Because magic-8-ball testers are built for one thing: a quick pass/fail test for brand new wiring you just installed.



                          Obviously, in new wiring, you don't have a bunch of the kinds of problems you have in old wiring, like people bootlegging ground off neutral. The device is simply not made to solve those problems.



                          So if you misuse the tool to test old wiring, the reports (what it says on the label) will often be misleading, and will send you on wild goose chases. That's why I call it a magic 8-ball tester! An actual magic-8-ball would be about as reliable. It is useful in two ways:




                          • The lights themselves can give you hints (provided you know how they are connected, see manassehkatz's discussion)

                          • The "GFCI test" button can be helpful when testing downline receptacles fed off a GFCI elsewhere.


                          With old wiring there's no substitute for opening it up and having a look.






                          share|improve this answer






























                            1












                            1








                            1







                            Yes, it will misread. Because magic-8-ball testers are built for one thing: a quick pass/fail test for brand new wiring you just installed.



                            Obviously, in new wiring, you don't have a bunch of the kinds of problems you have in old wiring, like people bootlegging ground off neutral. The device is simply not made to solve those problems.



                            So if you misuse the tool to test old wiring, the reports (what it says on the label) will often be misleading, and will send you on wild goose chases. That's why I call it a magic 8-ball tester! An actual magic-8-ball would be about as reliable. It is useful in two ways:




                            • The lights themselves can give you hints (provided you know how they are connected, see manassehkatz's discussion)

                            • The "GFCI test" button can be helpful when testing downline receptacles fed off a GFCI elsewhere.


                            With old wiring there's no substitute for opening it up and having a look.






                            share|improve this answer















                            Yes, it will misread. Because magic-8-ball testers are built for one thing: a quick pass/fail test for brand new wiring you just installed.



                            Obviously, in new wiring, you don't have a bunch of the kinds of problems you have in old wiring, like people bootlegging ground off neutral. The device is simply not made to solve those problems.



                            So if you misuse the tool to test old wiring, the reports (what it says on the label) will often be misleading, and will send you on wild goose chases. That's why I call it a magic 8-ball tester! An actual magic-8-ball would be about as reliable. It is useful in two ways:




                            • The lights themselves can give you hints (provided you know how they are connected, see manassehkatz's discussion)

                            • The "GFCI test" button can be helpful when testing downline receptacles fed off a GFCI elsewhere.


                            With old wiring there's no substitute for opening it up and having a look.







                            share|improve this answer














                            share|improve this answer



                            share|improve this answer








                            edited 5 hours ago

























                            answered 6 hours ago









                            HarperHarper

                            91.2k6 gold badges66 silver badges188 bronze badges




                            91.2k6 gold badges66 silver badges188 bronze badges

































                                draft saved

                                draft discarded




















































                                Thanks for contributing an answer to Home Improvement Stack Exchange!


                                • Please be sure to answer the question. Provide details and share your research!

                                But avoid



                                • Asking for help, clarification, or responding to other answers.

                                • Making statements based on opinion; back them up with references or personal experience.


                                To learn more, see our tips on writing great answers.




                                draft saved


                                draft discarded














                                StackExchange.ready(
                                function () {
                                StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f171022%2fcan-the-ground-attached-to-neutral-fool-a-receptacle-tester%23new-answer', 'question_page');
                                }
                                );

                                Post as a guest















                                Required, but never shown





















































                                Required, but never shown














                                Required, but never shown












                                Required, but never shown







                                Required, but never shown

































                                Required, but never shown














                                Required, but never shown












                                Required, but never shown







                                Required, but never shown







                                Popular posts from this blog

                                Taj Mahal Inhaltsverzeichnis Aufbau | Geschichte | 350-Jahr-Feier | Heutige Bedeutung | Siehe auch |...

                                Baia Sprie Cuprins Etimologie | Istorie | Demografie | Politică și administrație | Arii naturale...

                                Nicolae Petrescu-Găină Cuprins Biografie | Opera | In memoriam | Varia | Controverse, incertitudini...